JVT-3789:
ONE (1) 2500 KVA GENERAL ELECTRIC (ABB) INDOOR DRY TYPE TRANSFORMER,
TYPE CS20, 3 PHASE, 60 HERTZ, CLASS OA, 80 DEGREE C RISE, 5.47%
IMPEDANCE, COPPER CAST COIL WINDINGS, TEMPERATURE CONTROL SYSTEM
SERIES 21, INST. BOOK OMM XFR 1280, HV RIGHT X LV LEFT FACING
NAMEPLATE, MFG. 1997, S/N P100993-60162-09
HIGH VOLTAGE: 4160 D BIL: 75 KV
LOW VOLTAGE: 480Y/277 BIL: 30 KV
TAPS: 4368-4264-4160-4056-3952
TOTAL WEIGHT: 18,000 LBS.
CORE & COILS: 15,500 LBS.
DIMENSIONS: 114"H X 126"L X 66"W
CORE & COILS: 93"H X 114"L X 46.5"W
LOWEST REMOVABLE HEIGHT: 83.25"
***2500/3333 CAPACITY AVAILABLE WITH FANS FOR AN ADDITIONAL COST***<